How can you test that the control unit for the smoke detector is working?
The easiest way to test that the control unit is working is to remove the smoke detector loop from the control unit and instead to connect the termination resistor to the same terminals. The termination resistor is usually connected to the final smoke detector in the loop. If there is only one smoke detector in the loop, the termination resistor will be there. You do not, of course, have to locate the system’s termination resistor – you can use one of your own for this test.
PLEASE NOTE! Make sure that the test produces the correct resistance value. See the list below:
Control unit | Resistor |
ABAV-230V | 2,2 kOhm |
ABAV-S (24 och 230Vac) | 2,2 kOhm |
ABAV-S3 (24 och 230Vac) | 2,2 kOhm |
ABV-3 (24Vac) | 2,2 kOhm |
ABDS-400 | 560 Ohm |
ABDS-500 | 2,2 kOhm |
KE-600 | 2,2 kOhm |